Diesel Fuelled Range, P200H/P220HE
|
| OUTPUT RATINGS |
| Generating Set Model |
P200H/P220HE |
| | Prime | Standby |
|
380 - 415 Volts, 50 Hz
|
200 kVA
160 kW |
220 kVA
176 kW |
| 480 Volts, 60 Hz |
225 kVA
180 kW |
250 kVA
200 kW |
Standard reference conditions 27ºC (80ºF) Air
Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity.
SOUND ATTENUATED (SA) MODELS
Sound Pressure Levels (dBA) at 1500 RPM (50Hz) |
| % Load |
15 metres |
7 metres |
1 metre |
| 75% |
65.5 |
73 |
84 |
| 100% |
67 |
73 |
84 |
SOUND ATTENUATED (SA) MODELS
Sound Pressure Levels (dBA) at 1800 RPM (60Hz) |
| % Load |
15 metres |
7 metres |
1 metre |
| 75% |
68 |
76 |
86 |
| 100% |
70 |
76 |
86 |
| WEIGHTS AND DIMENSIONS |
| |
OPEN |
SA |
| Length: mm |
2953 |
3900 |
| Width: mm |
1003 |
1300 |
| Height: mm |
1717 |
2035 |
| Weight: kg |
2009 |
2857 |
|
|