POWER, ANYWHERE, ANYTIME
  MACFARLANE GENERATORS   FGWilson P40P1/P44E1
 

Diesel Fuelled Range, P40P1/P44E1

OUTPUT RATINGS
Generating Set Model P40P1/P44E1
 PrimeStandby
380 - 415 Volts, 50 Hz 40 kVA
32 kW
44 kVA
35.2 kW
480 Volts, 60 Hz 45 kVA
36 kW
50 kVA
40 kW
Standard reference conditions 27ºC (80ºF) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity.

 
SOUND ATTENUATED (SA) MODELS
Sound Pressure Levels (dBA) at 1500 RPM
(50Hz)
% Load 15 metres 7 metres 1 metre
75% 64 70 81
100% 64 70 81.5

 
SOUND ATTENUATED (SA) MODELS
Sound Pressure Levels (dBA) at 1800 RPM
(60Hz)
% Load 15 metres 7 metres 1 metre
75% 67 73 84
100% 68 74 85

 
WEIGHTS AND DIMENSIONS
  OPEN SA
Length: mm 2149 2250
Width: mm 710 1130
Height: mm 1341 1646
Weight: kg 800 1260