POWER, ANYWHERE, ANYTIME
  MACFARLANE GENERATORS   Petbow Cummins B3.31 Series
 

Petbow Generating Sets Powered By

Cummins B3.3l Series

Diesel Engines

Model

Prime

kW(kVA)

Standby

kW(kVA)

Engine

Model

CB-26A

26 (32)

30 (37)

B3.3G1

CP-40A

40 (50)

44 (55)

B3.3G2


Circuit Breaker Cubicle

3-pole moulded case circuit breaker with optional shunt trip and auxiliary contacts.

Finish
High gloss green finish.

General
Set of operating and instruction manuals.

Options
Refer distributor for range details.

Optional MONZA Acoustic Enclosure

- 70 dBA @ 7 metres (average). - 4 point lift and skid ends standard. - Central lifting frame optional. - Lockable doors. - Vertical air discharge. - Compact footprint design.

 

12 Lite Detector Control Panel

Controls generator set start and shutdown.
Automatic remote start.
DC panel lighting.
Panel mounted on vibration isolators.
Analog gauges display performance trends.
Panel Standard Specification
Run-stop-remote switch.
Automatic remote starting, 2 wire.
Coolant temperature gauge.
Oil pressure gauge.
DC voltmeter.
Running time meter.
Fault reset switch.
Lamp test switch.
AC voltmeter / ammeter with selector switch.
Dual scale frequency meter / tachometer.
Emergency stop.
Engine monitoring and shutdown for:
- low oil pressure
- high coolant temperature
- over crank
- over speed
- low coolant level
Common external alarms

Engine

Cummins B3.3L, 4 cylinder, diesel engines. 500C radiator. 12 Volt starting, battery charge alternator. Set mounted silencer. Spin-on replaceable element fuel and oil filters. Mechanical governor. (electronic optional). Dry element air filter.
Alternator

Brushless, single bearing, revolving field. 4-pole screen protected drip proof. Class H insulation. Rotor and exciter impregnated with tropical grade insulating polyester resin. Epoxy coated stator winding. Sealed solid state automatic voltage regulator. Optional permanent magnet exciter.

Chassis

Fabricated and welded chassis. Builtin anti-vibration mountings. In-skid fuel tank. Flexible fuel lines.

Technical Data

Generating Sets

Set model

CB-26A

CP-40A

Prime rating*

26kWe 32kVA

40kWe 50kVA

Standby rating"

30kWe 37kVA

44kWe 55kVA

Set output

380/415V 50 Hz

380/415V 50 Hz

Engine make

Cummins

Cummins

Model

B3.3G1

B3.3G2

Cylinders

Four

Four

Engine configuration

In-line

In-line

Governor / class

Mechanical/A1

Mechanical/A1

Aspiration

Naturally

Naturally

Bore and stroke

95mm x 115mm

95mm x 115mm

Compression ratio

18.2:1

17:1

Cubic capacity

3.26 Litres

3.26 Litres

Cranking current @ -18°c

550A

550A

Engine Output-Prime

31.1 kWm

45.3 kWm

Nett at flywheel- standby

34.8 kWm

49.7 kWm

Max. load acceptance - single steps

100%

100%

Alternator size (Prime)

UC1224C

UC1224E

Alternator voltage regulation

±1.5%

±1.5%

Alternator insulation class

H

H

Fuel consumption (Prime) 100% load

7.8 L/hr

11.8 L/hr

Fuel consumption (Standby) 100% load

9.0 L/hr

13.6 L/hr

Lubrication oil consumption

0.5% of fuel consumption

0.5% of fuel consumption

Lubrication oil capacity

8Litres

8 Litres

In-skid fuel tank capacity-open set

110 Litres

110 Litres

Fuel tank capacity - MONZA canopy

450 Litres

450 Litres

Coolant capacity-radiator and engine

11.5 Litres

14 Litres

Exhaust temp-full load

450°C

475°C

Exhaust gas flow-full load prime

0.949M3/s, 341.5M3/hr

0.1369m3/s, 492.71 m3/hr

Exhaust gas back pressure max

10.2 kPa, 76mm Hg

10.2 kPa, 76mm Hg

Air flow-radiator (50°C ambient)

2.18M3/s, 7868m3/hr

5.23 m3/s, 8889M3/hr

Air flow - engine intake

0.0349M3/s, 125.7M3/hr

0.0489M3/s, 176m3/hr

Heat radiated to ambient

10.1 kW

15.4 kW

Derating factors - temp.

2% per 10°C above 40°C

4.5% per 10°C above 40°C

Derating factors - altitude

0.7% per 100m above 1 OOOm

0.9% per 100 m above 1000m

1. Data based on engine operating at full working temperatures, at 1500 rpm (50 Hz).
2. The above figures are representative of an engine test only, and cannot be construed as a guarantee by Cummins Engine Co. Ltd. They should therefore be used for guidance only.
3. Generator sets operating in standby applications may require engine coolant heaters - please contact Distributor for details.

* Prime: Continuous running at variable load for unlimited periods with 10% overload available fort hour in any 12 hour period.

** Standby: Continuous running at variable load for duration of emergency.

Environmental conditions for set running ratings 400c ambient, 152.4m above sea level, 60% relative humidity. Voltages: Standard 380-450V.

Compliance Standards: To BS4999/5000 pt 99, VDE 0530, UTE51 000, NEMA MG1-22, CEMA, IEC 34, CSA A22.2, AS1359, BS5514, ISO 2046 and ISO 8528.

 