Model

Prime

kW(kVA)

Standby

kW(kVA)

Engine

Model

BG-51A

51 (64)

56 (70)

4BT3.9G2

BK-68A

68 (85)

75 (94)

6BT5.9G2

BF-85A
85 (106)
95 (119)
6BT5.9G2

 


Circuit Breaker Cubicle

3-pole moulded case circuit breaker with optional shunt trip and auxiliary contacts.

Finish
High gloss green finish.

General
Set of operating and instruction manuals.

Options
Refer distributor for range details.

Optional MONZA Acoustic Enclosure

- 70 dBA @ 7 metres (average). - 4 point lift and skid ends standard. - Central lifting frame optional. - Lockable doors. - Vertical air discharge. - Compact footprint design.

 

12 Lite Detector Control Panel

Controls generator set start and shutdown.
Automatic remote start.
DC panel lighting.
Panel mounted on vibration isolators.
Analog gauges display performance trends.
Panel Standard Specification
Run-stop-remote switch.
Automatic remote starting, 2 wire.
Coolant temperature gauge.
Oil pressure gauge.
DC voltmeter.
Running time meter.
Fault reset switch.
Lamp test switch.
AC voltmeter / ammeter with selector switch.
Dual scale frequency meter / tachometer.
Emergency stop.
Engine monitoring and shutdown for:
- low oil pressure
- high coolant temperature
- over crank
- over speed
- low coolant level
Common external alarms

Engine

Cummins 4BT3.9G2 and 6BT5.9G2 in-line 4 and 6 cylinder, diesel engines. 50°C radiator. 12 Volt starting, battery charge alternator. Set mounted silencer. Spin-on replaceable element fuel and oil filters. Mechanical governor. (electronic optional). Dry element air filter.
Alternator

Brushless, single bearing, revolving field. 4-pole screen protected drip proof. Class H insulation. Rotor and exciter impregnated with tropical grade insulating polyester resin. Epoxy coated stator winding. Sealed solid state automatic voltage regulator. Optional permanent magnet exciter.

Chassis

Fabricated and welded chassis. Builtin anti-vibration mountings. In-skid fuel tank. Flexible fuel lines.



 

Technical Data

Generating Sets

Set model

BG-51A

BK-68A

BF-85A

Prime rating"

51 kWe 64kVA

68kWe 85kVA

85kWe 106kVA

Standby rating**

56kWe 70kVA

75kWe 94kVA

95kWe 119kVA

Set output

380/415V 50 Hz

380/415V 50 Hz

380/415V 50 Hz

Engine make

Cummins

Cummins

Cummins

Model

4BT3.9G2

6BT5.9G2

6BT5.9G2

Cylinders

Four

Six

Six

Engine configuration

In-line

In-line

In-line

Governor / class

Mechanical/A1

Mechanical/A1

Mechanical/A1

Aspiration

Turbocharged

Turbocharged

Turbocharged

Bore and stroke

102mm x 120mm

105mm x 120mm

102mm x 120mm

Compression ratio

16.5:1

16.5:1

17.5:1

Cubic capacity

3.92 Litres

5.88 Litres

5.88 Litres

Cranking current @ 0°c

625A

625A

625A

Engine Output-Prime

56 kWm

76 kWm

94 kWm

Nett at flywheel- standby

62 kWm

83 kWm

103 kWm

Max. load acceptance - single steps

40 kWe

54 kWe

65 We

Alternator size (Prime)

UC1224F

UC1274C

UC1274D

Alternator voltage regulation

±1.0°/a

±1.0%

±1.0%

Alternator insulation class

H

H

H

Fuel consumption (Prime) 100% load

15.37 L/hr

19.8 L/hr

24.07 L/hr

Fuel consumption (Standby) 100% load

16.88 L/hr

21.7 L/hr

26.87 L/hr

Lubrication oil consumption

0.5% of fuel consumption

0.5% of fuel consumption

0.5°/a of fuel consumption

Lubrication oil capacity

11 Litres

16 Litres

16 Litres

In-skid fuel tank capacity-open set

210 Litres

220 Litres

220 Litres

Fuel tank capacity - MONZA canopy

450 Litres

600 Litres

600 Litres

Coolant capacity-radiator and engine

19 Litres

25 Litres

25 Litres

Exhaust temp-full load

521 °C

510°C

577°C

Exhaust gas flow-full load prime

0.158M3/s, 569M3/hr

0.2383/s, 842M3/hr

0.283m3/s, 1020M3/hr

Exhaust gas back pressure max

10.2 kPa, 76mm Hg

10.2 kPa, 76mm Hg

10.2 kPa, 76mm Hg

Air flow-radiator (50°C ambient)

2.26m3/s, 8136m3/hr

1.6m3/s, 5760M3/hr

2.1 m3/s, 7560m3/hr

Air flow - engine intake

0.057m3/s, 2053/hr

0.085M3/s, 306M3/hr

0.094m3/s, 338M3/hr

Heat radiated to ambient

15 kW

20 kW

22 kW

Derating factors - temp.

2% per 11 °C above 40°C

2% per 11 °C above 40°C

2% per 11 °C above 40°C

Derating factors - altitude

4% per 300m above 150m

4% per 300m above 1370m

4% per 300m above 150m

1. Data based on engine operating at full working temperatures, at 1500 rpm (50 Hz).

2. The above figures are representative of an engine test only, and cannot be construed as a guarantee by Cummins Engine Co. Ltd. They should therefore be used for guidance only.

3. Generator sets operating in standby applications may require engine coolant heaters - please contact Distributor for details.

* Prime: Continuous running at variable load for unlimited periods with 10% overload available fort hour in any 12 hour period.

** Standby: Continuous running at variable load for duration of emergency.

Environmental conditions for set running ratings 400c ambient, 152.4m above sea level, 60% relative humidity. Voltages: Standard 380-450V.

Compliance Standards: To BS4999/5000 pt 99, VDE 0530, UTE51 000, NEMA MG1-22, CEMA, IEC 34, CSA A22.2, AS1359, BS5514, ISO 2046 and ISO 8528.

 